Login

Device Description

Product Name: FGS-221
Brand Name: Fibar
Product Line:
Product Code: FGS221- 2 * 1.5KW
Product Version:
Product Comment:
Battery Type:
Battery Count:
Description: Very thin and little wall insert to be mounted behind a standard switch
Inclusion Note: Tripple Press little button on device
Wakeup Note:
 
Default Image: Not available

Device Data

Hash Weak: 04-10-01
Hash Strong: 010f-0200-0103-03-03-14-01-03
Manufacturer: Fibargroup (0x010F)
Product Type ID: 0x0200
Product ID: 0x0103
Library Type: 0x03
Protocol Version: 0x03
Protocol Sub Version: 0x14
Application Version: 0x01
Application Sub Version: 0x03
Basic Class: Slave with routing capabilities
Generic Class: Binary Switch
Specific Class: Binary Power Switch
Optional Flag: Yes
Listening Flag: Yes
Routing Flag: Yes
Beam Sensor 0
RF Frequency
Certification ID:
Certification Number:
Submitter: cpae
Create time: 2012-12-03 11:25:42
Last changed: 2012-12-03 11:29:58

Implemented Command Classes

Command Class Byte Version Support Control In NIF Secure Non Secure
Basic 0x20 1 Yes No No No Yes
No Operation 0x00 0 Yes No No No Yes
Binary Switch 0x25 1 Yes No Yes No Yes
Version 0x86 1 Yes No Yes No Yes
All Switch 0x27 1 Yes No Yes No Yes
Multi Channel 0x60 2 Yes No Yes No Yes
Multi Channel Association 0x8E 2 Yes No Yes No Yes
Configuration 0x70 1 Yes No Yes No Yes
Manufacturer Specific 0x72 1 Yes No Yes No Yes
Powerlevel 0x73 1 Yes No Yes No Yes
Association 0x85 2 Yes No Yes No Yes

Config Parameters

Paramter No. 1 Size 1 Default -1
Name All on/off function
Description Enables or disabled the all on / all off function
Type constant
Values
0   ->   neither ALL ON nor ALL OFF are active
1   ->   only ALL OFF is active
2   ->   only ALL ON is active
-1   ->   ALL ON and ALL OFF are active
 
Paramter No. 3 Size 1 Default 0
Name Automatic Switching Off after defined time
Description Allows to automatically turn off the relais after a fixed time set in parameter 4
Type constant
Values
0   ->   Disabled
1   ->   Enabled for relays 1, disabled for relays 2
2   ->   Enabled for relays 2, disabled for relays 1
3   ->   Enabled
 
Paramter No. 4 Size 1 Default -56
Name Automated Turn Off Time for relays 1
Description defines the time to turn off the relais 1in case parameter no 3 is enabled
Type constant
Values
0 - -1   ->   ms
 
Paramter No. 5 Size 1 Default -56
Name Automated Turn Off Time for relays 2
Description defines the time to turn off the relais 2 in case parameter no 3 is enabled
Type constant
Values
0 - -1   ->   ms
 
Paramter No. 6 Size 1 Default 0
Name Commands Sent to Association Group 1
Description Defines what status changes cause sending out a wireless command. Zu allow double click function parameter 15 needs to be turned to 1
Type rangemapped
Values
0   ->   turning on and turning off sends out a wireless command
1   ->   Turning off sends a wireless command. All devices can be turned on using a double click, dimmers will return to their last dimming state.
2   ->   Turning ff sends a wireless command. All devices can be turned on using a double click, dimmers will dim to 100 %.
 
Paramter No. 7 Size 1 Default 1
Name Check status before sending a control command on external switch no 2.
Description When external switch no 2 is switches the status of the remote device to be switches is checked or not.
Type rangemapped
Values
0   ->   Not checked
1   ->   Checked
 
Paramter No. 13 Size 1 Default 0
Name Bistable Switch State
Description Defines the behavior of a connected bistable switch
Type constant
Values
0   ->   ON/OFF sets to change of key state
1   ->   ON is active when contacts are closed and OFF is active when contacts are open
 
Paramter No. 14 Size 1 Default 0
Name Type of Switch
Description Defines the type of switch attached to the device
Type constant
Values
0   ->   mono-stable switch
1   ->   bi-stable switch
 
Paramter No. 16 Size 1 Default 0
Name Saving of switch state after power-down
Description The device will or will not return to the last switch state after a power down
Type constant
Values
0   ->   not return to previous state
1   ->   return to previous state
 
Paramter No. 30 Size 1 Default 3
Name General Alarm Set - Relay 1
Description This defines the behavior of relay 1 in case of general alarms
Type constant
Values
0   ->   Deactivated, devices does not react to alarms
1   ->   Disable on Alarm - will switch off in case of alarm
2   ->   Enable on Alarm - will switch on in case of alarm
3   ->   Flashing on Alarm - will switch on and off periodically for 10 minutes
 
Paramter No. 31 Size 1 Default 2
Name Flood Alarm Set - Relay 1
Description This defines the behavior of relay 1 in case of flood alarms
Type constant
Values
0   ->   Deactivated, devices does not react to alarms
1   ->   Disable on Alarm - will switch off in case of alarm
2   ->   Enable on Alarm - will switch on in case of alarm
3   ->   Flashing on Alarm - will switch on and off periodically for 10 minutes
 
Paramter No. 32 Size 1 Default 3
Name Smoke Alarm Set - Relay 1
Description This defines the behavior of relay 1 in case of smoke alarms
Type constant
Values
0   ->   Deactivated, devices does not react to alarms
1   ->   Disable on Alarm - will switch off in case of alarm
2   ->   Enable on Alarm - will switch on in case of alarm
3   ->   Flashing on Alarm - will switch on and off periodically for 10 minutes
 
Paramter No. 33 Size 1 Default 1
Name Temperature Alarm Set - Relay 1
Description This defines the behavior of relay 1 in case of temperature alarms
Type constant
Values
0   ->   Deactivated, devices does not react to alarms
1   ->   Disable on Alarm - will switch off in case of alarm
2   ->   Enable on Alarm - will switch on in case of alarm
3   ->   Flashing on Alarm - will switch on and off periodically for 10 minutes
 
Paramter No. 39 Size 2 Default 600
Name Time of Active Alarm
Description Defines how long a alarm shall be active
Type range
Values
0 s - 20000 s   ->   Seconds
 
Paramter No. 40 Size 1 Default 3
Name General Alarm Set - Relay 2
Description This defines the behavior of relay 2 in case of general alarms
Type constant
Values
0   ->   Deactivated, devices does not react to alarms
1   ->   Disable on Alarm - will switch off in case of alarm
2   ->   Enable on Alarm - will switch on in case of alarm
3   ->   Flashing on Alarm - will switch on and off periodically for 10 minutes
 
Paramter No. 41 Size 1 Default 2
Name Flood Alarm Set - Relay 2
Description This defines the behavior of relay 2 in case of flood alarms
Type constant
Values
0   ->   Deactivated, devices does not react to alarms
1   ->   Disable on Alarm - will switch off in case of alarm
2   ->   Enable on Alarm - will switch on in case of alarm
3   ->   Flashing on Alarm - will switch on and off periodically for 10 minutes
 
Paramter No. 42 Size 1 Default 3
Name Smoke Alarm Set - Relay 2
Description This defines the behavior of relay 2 in case of smoke alarms
Type constant
Values
0   ->   Deactivated, devices does not react to alarms
1   ->   Disable on Alarm - will switch off in case of alarm
2   ->   Enable on Alarm - will switch on in case of alarm
3   ->   Flashing on Alarm - will switch on and off periodically for 10 minutes
 
Paramter No. 43 Size 1 Default 1
Name Temperature Alarm Set - Relay 2
Description This defines the behavior of relay 2 in case of temperature alarms
Type constant
Values
0   ->   Deactivated, devices does not react to alarms
1   ->   Disable on Alarm - will switch off in case of alarm
2   ->   Enable on Alarm - will switch on in case of alarm
3   ->   Flashing on Alarm - will switch on and off periodically for 10 minutes
 

Association Groups

Group Number Max Nodes Description
3 1
2 16 external Switch No 2
1 16 external Switch No 1

Endpoints

Number Name Description Dynamic Generic Specific Classes
2 No Binary Switch Binary Power Switch
Basic
...
1 No Binary Switch Binary Power Switch
Basic
...

Alarm Mappings

 